This article discusses NEC 2023 or 2026. ZinaVee's calculators use NEC 2017.
Published: June 2026 Technical Level: Advanced Category: Power Systems Design
Industrial facility power distribution at medium voltage (typically 4.16 kV, 13.8 kV, or 34.5 kV) introduces design requirements that are qualitatively different from low-voltage commercial distribution: arc flash energy levels that demand rigorous PPE boundaries and remote racking procedures, motor starting methods that must limit voltage dip to protect sensitive process controls, harmonic mitigation at medium voltage where capacitor bank resonance can amplify 5th and 7th harmonic currents to damaging levels, and protection coordination schemes that must handle both high-impedance ground faults (typical of resistance-grounded MV systems) and low-impedance three-phase faults with very different protective device responses. This paper develops the engineering methodology for each of these design domains, applied to a continuous-process manufacturing facility with a 13.8 kV distribution network, four 2.5 MVA unit substations, and a mix of large motor loads up to 1,500 hp.
The transition from low-voltage (480V) to medium-voltage (4.16–34.5 kV) distribution is driven by economic and technical considerations that intersect at approximately 1.5 to 2 MW of connected load per distribution bus. Above this threshold, the losses in 480V feeders become prohibitive, conductor ampacity limits require parallel runs that complicate installation, and the available fault current at 480V buses can approach or exceed the interrupting rating of standard molded-case circuit breakers. Medium-voltage distribution resolves these constraints by reducing current by a factor of approximately 9 to 29 compared to 480V service, but it introduces arc flash energy levels (typically 40 to 80 cal/cm² at 13.8 kV switchgear), protection coordination complexity at both the medium-voltage and the unit substation low-voltage level, and motor starting requirements that must be explicitly analyzed for every motor above approximately 100 hp.
This paper presents the engineering design methodology for a 13.8 kV industrial distribution system serving a continuous-process manufacturing facility with a total connected load of 8.4 MVA. The facility includes large centrifugal compressors (two at 1,500 hp, one at 800 hp), cooling tower pump and fan drives (16 motors from 50 to 250 hp), and a variable-production electrochemical process line with 12 rectifier assemblies producing significant harmonic content.
The 13.8 kV distribution system is configured as a radial network fed from a utility service entrance at 69 kV, stepped down through a 12 MVA, 69/13.8 kV main power transformer. The medium-voltage bus is divided into two sections (Bus A and Bus B) separated by a normally-open bus tie breaker, providing operational flexibility for maintenance and fault isolation without parallel operation during normal running, a configuration that simplifies relay coordination by maintaining a single source for each bus section under normal conditions.
Four 2.5 MVA, 13.8 kV/480V unit substation transformers are connected to the 13.8 kV bus: two to Bus A (serving the compressor building and process building west) and two to Bus B (serving the process building east and utilities building). Each unit substation feeds a 480V MCC that serves the motors and process controls in its zone.
The 13.8 kV system is high-resistance grounded (HRG) through a zig-zag grounding transformer and a neutral grounding resistor (NGR) sized to limit single-line-to-ground fault current to 5 A primary:
Where: is the line-to-neutral voltage in volts.
is the rated ground fault current limit in amperes (5 A is the NEC maximum for high-resistance grounding per NEC 2023 Section 250.36).
is the required neutral grounding resistor value in ohms.
The HRG philosophy allows the 13.8 kV system to continue operating through the first ground fault: a single-phase-to-ground fault in HRG system does not produce dangerous fault current, and the process can be safely shut down for maintenance rather than tripping immediately. The HRG system includes continuous ground fault monitoring relays that alarm on first ground fault detection, allowing the process operators to initiate a controlled shutdown before a second fault develops and creates a phase-to-phase fault condition that would require immediate clearing.
Large motor starting draws inrush current of 5 to 7 times the motor's full-load current for direct-on-line (DOL) starting. This inrush creates a voltage dip at the motor bus that must be maintained within limits acceptable to process controls, motor contactors, and other sensitive equipment. NEMA MG-1 Section 12.48 specifies that motor starter contactors must hold-in at 85 percent of rated voltage; process instrumentation and variable frequency drives typically require 90 percent or higher.
The voltage dip at the bus during motor starting is:
Where: is the voltage dip in per unit of rated bus voltage.
is the motor starting current (locked-rotor current) in amperes.
is the three-phase short-circuit current available at the bus in amperes.
is the rated bus voltage.
For the 1,500 hp compressor motor on the 13.8 kV bus: full-load current is 60 A, locked-rotor current is 420 A (7× FLA), three-phase fault current at the 13.8 kV bus is 4,200 A. The DOL voltage dip is:
Where: is 0.10 per unit, meaning the bus voltage drops to 90% of rated during the starting event.
A 10 percent voltage dip at the 13.8 kV bus propagates through the unit substation transformers to the 480V buses at a reduced but non-negligible level, approximately 8 percent dip at the 480V bus, which is marginal for NEMA MG-1 contactor hold-in requirements. The design added a solid-state reduced-voltage starter (SSRVS) for each 1,500 hp motor, limiting the starting current to approximately 3.5× FLA (210 A) and reducing the 13.8 kV bus voltage dip to 5 percent.
The transient voltage depression during the largest motor start is illustrated in Figure 1, which plots the bus voltage through the start and recovery.

Figure 1. Bus voltage during a large motor start. The horizontal axis is time in seconds and the vertical axis is voltage in per unit. The voltage dips sharply as the motor inrush current is drawn against the source impedance, then recovers as the machine accelerates. The engineer should observe that the dip must remain above the ride-through tolerance of sensitive loads and contactors on the same bus (commonly about 0.80 p.u.), which can require a stiffer source, reduced-voltage starting, or segregating the motor onto a dedicated bus.
The twelve electrochemical process rectifier assemblies each draw 250 kVA at 0.85 power factor from the 480V bus, using 12-pulse rectifier topology (two six-pulse bridges with phase-shifted transformers). The characteristic harmonic orders for 12-pulse rectifiers are for integer : 11th, 13th, 23rd, 25th, and higher. The 11th harmonic current from each rectifier is approximately 9 percent of the fundamental, and the 13th is approximately 7 percent.
The total 11th harmonic current injected into the 480V bus from all twelve rectifiers is approximately 270 A (9 percent of 12 × 250 A fundamental). The IEEE 519-2022 harmonic current limit at the 480V PCC (inside the unit substation low-voltage secondary) is 4 percent for harmonic orders below the 11th and 2 percent for 11th through 16th, with a TDD limit of 8 percent. The 11th harmonic content at 270/3,000 = 9 percent of the maximum demand current significantly exceeds the 2 percent limit.
A passive 11th harmonic filter was designed for the 480V bus: a series LC circuit tuned to 660 Hz (11th harmonic at 60 Hz). The filter provides a low-impedance path for the 11th harmonic current and simultaneously provides approximately 400 kVAR of reactive power at 60 Hz, improving the bus power factor from 0.85 to approximately 0.97.
The filter capacitor is rated for the fundamental plus harmonic current:
Where: is the required filter capacitor current rating in amperes rms.
is the fundamental reactive current drawn by the filter at rated kVAR.
and are the per-unit 11th and 13th harmonic currents diverted through the filter.
Post-installation measurements confirmed 11th harmonic current at the 480V PCC reduced from 270 A to 38 A (1.3 percent of maximum demand), well within the IEEE 519-2022 limit.
The most consequential lesson of the 13.8 kV continuous-process design is that the four analyses an industrial distribution system demands (arc flash, motor starting, harmonics, and protection coordination) are not independent deliverables but coupled constraints that must be solved together. High-resistance grounding chosen for process continuity changes the ground-fault detection scheme; reduced-voltage starting chosen to hold contactor voltage changes the cable and protection ratings; the 12-pulse rectifier chosen for IEEE 519-2022 compliance changes the available fault current the protective devices must coordinate against. A design that optimizes each in isolation will violate one of the others.
The most common implementation failure is treating the harmonic study as a compliance afterthought run once at the point of common coupling, rather than as a design input that governs transformer sizing and filter placement from the outset. A facility that defers harmonic analysis until commissioning frequently discovers a resonance between power-factor capacitors and system inductance that was entirely predictable from the installed transformer impedance, and the retrofit cost of relocating or detuning the capacitor bank far exceeds the cost of having modeled it during design.
The engineer carrying this system forward should next quantify the interaction between the high-resistance grounding scheme and the arc flash incident energy on the 480 V secondary, because the ground-fault current that HRG deliberately limits also changes the clearing time of phase-to-ground arcing faults, the boundary condition where process-continuity grounding and personnel-safety arc flash analysis meet, and the one most often left unexamined.
The analysis in this paper connects to several companion studies in this library. Readers concerned with the upstream and downstream engineering will find Motor Starting Analysis develops a closely related aspect of the same problem, while Variable Frequency Drive Harmonic Mitigation in Manufacturing extends the treatment into an adjacent domain. For the broader methodological context, Commercial Building Electrical Systems provides complementary depth.
[1] NFPA 70, National Electrical Code, Articles 250, 430, and 670, 2023 edition, NFPA, 2023.
[2] IEEE Standard 519-2022, IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems, IEEE, 2022.
[3] NEMA MG-1-2021, Motors and Generators, NEMA, 2021.
[4] IEEE Standard 141-1993 (Red Book), IEEE Recommended Practice for Electric Power Distribution for Industrial Plants, IEEE, 1993.
[5] IEEE Standard 242-2001 (Buff Book), IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, IEEE, 2001.
[6] ANSI/IEEE C57.110-2018, IEEE Recommended Practice for Establishing Transformer Capability when Supplying Non-Sinusoidal Load Currents, IEEE, 2018.
[7] J. Burke, Power Distribution Engineering: Fundamentals and Applications, Marcel Dekker, 1994.
[8] IEEE Standard 1584-2018, IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE, 2018.