Published: June 2026 Technical Level: Advanced Category: Protection Systems
Substation grounding grid design is governed by IEEE Standard 80-2013, Guide for Safety in AC Substation Grounding, which establishes the tolerable limits for step and touch voltages experienced by personnel during ground fault events and provides a systematic design procedure for ensuring those limits are not exceeded. The hazard mechanism is straightforward: when fault current flows through the grounding system, potential differences develop across the resistive soil between points on the earth's surface, and between grounded metallic structures and the earth's surface at their base. A person contacting these potential differences completes a current path through the body that can cause ventricular fibrillation if the body current exceeds the fibrillation threshold. This paper develops the IEEE 80-2013 design procedure from first principles, presents the tolerable voltage calculations for a representative 115 kV/13.8 kV substation, evaluates the impact of surface material selection on tolerable limits, and derives the grounding grid parameters required to meet the design criteria. The procedure demonstrates that for the case study configuration (28.4 kA available ground fault current), a 10-cm crushed rock surface layer increases the tolerable touch voltage from 111 V to 867 V, changing the design requirement from impractical to achievable with a standard grid design.
The grounding system of an electric power substation serves three distinct engineering functions: providing a low-impedance path for fault current to return to the source, maintaining the potential of grounded metallic structures within safe limits relative to the local earth potential during fault events, and limiting the potential gradient in the soil surface near grounded structures to safe levels for personnel standing on or near the substation grade. The first function is addressed through conductor sizing per IEEE 80 Section 11. The second and third functions, touch and step voltage compliance, are the subjects of this paper.
The physical mechanism of step and touch voltage hazard is that ground fault current flowing through the soil creates a potential distribution that is not uniform. Near the point where fault current enters the earth, the potential is highest; at distances far from the fault, the potential approaches zero. The gradient of this potential distribution, the rate at which voltage changes with distance, determines the step voltage experienced by a person whose two feet contact the earth at two different points. Simultaneously, the potential of grounded metallic structures (fence posts, equipment enclosures, disconnect switch handles) rises above the local earth potential at the point where the person is standing, creating a touch voltage hazard. Both hazards can cause ventricular fibrillation if the resulting body current exceeds the fibrillation threshold defined by Dalziel's equations.
The threshold body current for ventricular fibrillation is a function of the fault duration, based on Dalziel's energy-based model. For a 50 kg person (representing a small adult or child, the conservative case):
Where: is the permissible body current in amperes for a 50 kg person.
is the duration of the shock current in seconds.
For a 70 kg person, the coefficient is 0.157. IEEE 80-2013 uses the 50 kg threshold for all tolerable voltage calculations because it provides the conservative basis appropriate for design.
For a fault clearing time of 0.5 seconds, the permissible body current is A. For clearing times below 0.1 seconds, achievable with high-speed differential protection, the permissible body current increases to 0.367 A, and the resulting tolerable voltage limits are substantially higher, which has direct implications for grounding grid cost.
The touch voltage circuit model treats the human body as a resistance ohms in series with two hand-to-foot contact resistances. One contact resistance is the grounded structure (essentially zero for a well-bonded metallic structure). The other is the resistance of the earth surface material under the standing person's feet, modeled as the resistance of a foot contact (a circular plate of diameter 0.08 m) on a surface layer of resistivity . The resistance of this foot contact is ohms, and with two feet in parallel, the effective ground resistance in the touch voltage circuit is .
The tolerable touch voltage, defined as the maximum voltage across the body that keeps the body current below the fibrillation threshold, is:
Where: is the tolerable touch voltage in volts for a 50 kg person.
is the surface layer resistivity in ohm-meters (3,000 Ω·m for 10 cm crushed rock, 100 Ω·m for native soil).
is the fault clearing time in seconds.
For native soil ( Ω·m) and 0.5-second clearing time: V.
For 10 cm crushed rock ( Ω·m) and the same clearing time: V. The high-resistivity surface layer increases the tolerable touch voltage by a factor of 4.8, a profound engineering consequence that explains why crushed rock surfacing is standard practice in substation design.
The step voltage circuit places two foot contacts in series with the body. The two-foot series resistance is , and the tolerable step voltage is:
Where: is the tolerable step voltage in volts.
reflects the two-foot series resistance equivalent to per foot with a correction factor from IEEE 80 for the two-plate model.
For crushed rock surfacing and 0.5-second clearing: V. Step voltage limits are substantially more permissive than touch voltage limits for the same surface conditions, because the body current in the step voltage circuit flows through the legs rather than the chest, reducing the fibrillation risk for a given current magnitude.
The resistance of a grounding grid buried at depth in uniform soil of resistivity is estimated using the simplified Sverak formula:
Where: is the grid resistance in ohms.
is the soil resistivity in Ω·m.
is the total grid area in m².
is the total length of buried conductors including rods in meters.
is the burial depth in meters (typically 0.5 m).
For a 100 m × 60 m grid ( m²) with m total conductor, buried in soil with Ω·m at depth 0.5 m:
This ground resistance is used to calculate the ground potential rise (GPR), which is the product of the grid resistance and the symmetrical ground fault current flowing through the grid: . For kA (accounting for current division between the grid and overhead ground wires), V.
The actual touch and step voltages within the grounding grid are determined by the distribution of current through the soil, which depends on grid geometry: conductor spacing, number of ground rods, and burial depth. IEEE 80-2013 provides the mesh voltage formula for the worst-case touch voltage inside the grid (at the corner mesh):
Where: is the maximum mesh (touch) voltage in volts.
is the soil resistivity in Ω·m.
is the symmetrical grid current in amperes.
is the geometrical spacing factor, accounting for conductor spacing, depth, and number of parallel conductors.
is the irregularity factor, accounting for non-uniform current distribution.
is the effective buried conductor length contributing to mesh voltage control in meters.
The step voltage in the soil near the grid perimeter is:
Where: is the maximum step voltage in volts.
is the step voltage geometrical factor.
is the effective conductor length for step voltage in meters.
The design procedure iterates the grid geometry (conductor spacing , number of ground rods , rod length , and grid boundary shape) until both and are satisfied.
The case study substation has a 115 kV utility source with available three-phase fault current of 28.4 kA symmetrical at the HV bus. The grounding grid occupies a 90 m × 55 m area ( m²). Soil resistivity measurements per IEEE 81 (Wenner four-pin method at multiple electrode spacings) yield a two-layer model: upper layer resistivity Ω·m to 0.6 m depth, lower layer Ω·m below 0.6 m. For the simplified uniform soil analysis, IEEE 80 recommends using the upper layer resistivity as the conservative value: Ω·m.
The current division factor accounts for the fraction of total fault current that flows through the grounding grid versus through overhead ground wires and shield wires. For a fully shielded 115 kV line terminated at both ends with ground grid connections, the division factor is approximately 0.65, so A. The decrement factor for a 0.5-second fault duration and X/R ratio of 15 is 1.026, giving a design current of A.
The main protective relay operates in 3 cycles (0.05 seconds) with breaker interrupting time of 3 cycles, giving a total fault duration of 0.1 seconds. With s and crushed rock surfacing ( Ω·m):
With the initial grid design of 7.5 m conductor spacing, 24 ground rods at 3 m length, and 0.5 m burial depth, the computed mesh voltage is 1,847 V and the step voltage is 892 V. Both are below the tolerable limits (2,019 V touch, 6,973 V step), so the design is compliant.
The conductor sizing per IEEE 80 Section 11 requires that each conductor be sized to carry the fault current without exceeding the fusing temperature. For copper conductor in soil, the required conductor cross-section is:
Where: is the required conductor cross-section in kcmil.
is the fault duration in seconds.
is the maximum allowable conductor temperature (1,084°C for copper fusion).
is the ambient soil temperature.
is a material constant (234°C for copper).
For the design parameters above, the required conductor size is 2/0 AWG copper, which corresponds to a conductor cross-section well within the capacity of standard 4/0 AWG conductor typically specified for substation grids. The 4/0 AWG specification provides additional margin against corrosion-induced reduction in effective conductor cross-section over the system's design life.
The analysis in this paper connects to several companion studies in this library. Readers concerned with the upstream and downstream engineering will find Electrical Grounding Systems develops a closely related aspect of the same problem, while Lightning Protection Systems extends the treatment into an adjacent domain. For the broader methodological context, Utility Substation Modernization provides complementary depth.
IEEE Standard 80-2013 grounding analysis protects substation personnel by ensuring that the step and touch voltages developed across resistive soil during a ground fault remain below the tolerable limits set by the fibrillation threshold, and the 115 kV / 13.8 kV design example developed in this paper demonstrates the full sequence from tolerable-voltage determination through grid resistance and mesh-voltage calculation. The central engineering conclusion is that the tolerable voltage limits depend on the fault clearing time and the assumed body weight, so the grounding design cannot be verified independently of the protection system that determines how long the fault current flows: faster clearing relaxes the tolerable-voltage requirement and can permit a less extensive grid. For the practicing engineer, the operative takeaway is that grounding-grid design and protection coordination are coupled safety problems, that the mesh and step voltages must be computed for the actual fault current and duration the protection will allow, and that the design margin against the tolerable limits is the quantity that must be demonstrated, because the consequence of an inadequate grid is a lethal potential difference at a point a worker can contact.
[1] IEEE Standard 80-2013, Guide for Safety in AC Substation Grounding, IEEE, 2013.
[2] IEEE Standard 81-2012, Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System, IEEE, 2012.
[3] IEEE Standard 142-2007, Recommended Practice for Grounding of Industrial and Commercial Power Systems (Green Book), IEEE, 2007.
[4] ANSI/IEEE Standard 665-1995, Guide for Generating Station Grounding, IEEE, 1995.
[5] F. P. Dawalibi and D. Mukhedkar, "Optimum Design of Substation Grounding in a Two-Layer Earth Structure," IEEE Transactions on Power Apparatus and Systems, vol. PAS-94, no. 2, pp. 252–272, 1975.
[6] E. D. Sunde, Earth Conduction Effects in Transmission Systems, Van Nostrand, 1949 (Dover reprint, 1968).
[7] J. G. Sverak, "Simplified Analysis of Electrical Gradients Above a Ground Grid," IEEE Transactions on Power Apparatus and Systems, vol. PAS-103, no. 1, pp. 7–25, 1984.
[8] NFPA 70, National Electrical Code, Article 250, 2023 edition, NFPA, 2023.
[9] EPRI, Substation Grounding System Design, Technical Report EL-5203, EPRI, 1988.
[10] R. Hoerauf and N. Nichols, "Avoiding Transferred Earth Potentials in Grounding Designs," IEEE Transactions on Industry Applications, vol. 26, no. 4, pp. 739–745, 1990.